Polybraid 13.8KV

back
working voltage: 13.8Kv test voltage: 18Kv
construction:
- stranded conductor of tinned copper wire
- stranding class 5 IEC228 5
- core insulation made of silicone rubber
- Polyester braid
- Black Outer Sheath
application:
Suitable where PVC-insulated cables become brittle due to high temperature variations. Silicone-insulated single cores are preferably used in the metallurgical industry, steel works, hot-rolling mills, cooking plants, foundries, etc. The insulation consists of silicone rubber. lt is resistant to vegetable and animal fat, many types of oil and diluted acids. No decomposition occurs when exposed to alcohol, alkaline solutions, etc. The insulation is resistant to oxygen and ozone.
temperature range: - 60° C to + 180° C
temperature range short circuit conditions: to + 200° C

cores cross section outer diameter copper weight weight
mm˛ mm kg/100m
1 X 25 17.0 240.0 511.5
1 X 35 18.2 336.0 640.0
1 X 50 19.9 480.0 834.6
1 X 70 22.0 672.0 1096.2
1 X 95 24.0 912.0 1403.3
1 X 120 26.0 1152.0 1719.8


 

Please send your questions and comments to the following email: ryan@aptsa.co.za
Webdesign & Copyright © 2005 ryan jonsson. As of: